logo

Required Certificates For Inspection Process

Certificates required for Temporary and Final Certificates of Occupancy (where applicable):

  • Georgia Licensed Fire Sprinkler Contactor’s Material and Test Certificate for above ground piping
  • Georgia Licensed Fire Sprinkler Contactor’s Material and Test Certificate for below ground piping (flushing and pressure)
  • Georgia Licensed Fire Sprinkler Contactor’s Material Test Certificate for standpipes (200lb test)
  • Georgia Licensed Fire Sprinkler Contractor’s Certificate of Competency Site Supervision Form*
  • Fire Pump Test Certificate
  • Letter from fire alarm installer certifying installation and completed Inspection and Testing Form is in accordance with NFPA 72
  • Letter from the Mechanical Engineer certifying that the smoke evacuation system for atriums has been tested in accordance with NFPA 92B and meets the design criteria that was approved by the State Fire Marshal’s Office
  • Letter from a Georgia Licensed Special Hazard Suppression Company indicating the hood suppressions system is in compliance with NFPA 17A.
  • Letter from Georgia Licensed Electrician indicating that electrical system has been installed and meets the requirements of NFPA 70 (National Electrical Code)
  • Portable Fire Extinguishers installed and tagged by a Georgia Licensed Fire Extinguisher Company
  • All utilities must be on and in service (power, gas, water)
Movies by Moonlight
City Springs Event

Movies by Moonlight: A Goofy Movie

Friday, September 5
Enjoy a movie on the big screen under a beautiful night sky! Admission is free. A Goofy Movie will be showing Friday, September 5.
View Event
Blue Stone 5K-9
Recreational Program

Blue Stone 5K-9: A Road Race for People & Pups

Saturday, September 27
The Blue Stone 5K-9 will be a "pawsome" event happening during the Blue Stone Arts and Music Festival. Don't miss this tail-wagging good time with your "best friend!"
View Event